For electrical contractors, MEP engineers and home owners in Dubai, Sharjah, Abu Dhabi and Ajman. Enter the load current, cable run and conductor size in mm² on a 230 V or 400 V supply, and see the voltage drop in volts and per cent, plus the smallest standard cable size within your limit.
Worked example
With the calculator’s starting values:
| Supply | Single phase |
|---|---|
| Supply voltage | 230 V |
| Load current | 20 A |
| Cable length (one way) | 30 m |
| Method | Conductor resistance |
| Conductor size | 4 mm² |
| Conductor | Copper |
| Resistance increase at working temperature | 20 % |
| Allowed voltage drop | 5 % |
| Voltage drop | 6.19 V |
|---|---|
| Voltage drop | 2.69 % |
| Voltage at the load | 223.8 V |
| Within the allowed drop | Yes |
| Smallest standard size within the limit | 2.5 mm² |
How it is calculated
Single phase: voltage drop = 2 × current × length × resistivity ÷ conductor size
Three phase: voltage drop = √3 × current × length × resistivity ÷ conductor size
Resistivity = 0.0172 (copper) or 0.0282 (aluminium) Ω mm²/m at 20 °C × (1 + temperature increase)
Cable table method: voltage drop = mV/A/m × current × length ÷ 1,000
Per cent drop = voltage drop ÷ supply voltage × 100
The length is the one-way route length from the board to the load. The factor of 2 for single phase covers the line and neutral conductors; three phase uses √3 for the line-to-line drop on a balanced load.
Which method to use
The resistance method ignores cable reactance. For cables up to about 16 mm² resistance is the main part, so the result is close. For larger cables, and for a design you will submit, use the mV/A/m value from the cable maker’s data or the BS 7671 tables, which allow for reactance, the cable type and how it is installed.
Defaults you can change
The 20% resistance increase is a typical figure for a conductor running at 70 °C. The 11 mV/A/m and the 5% limit are example values: replace them with the cable data sheet and the limit in your specification. Voltage drop is only one check; the cable must also carry the current in the installed conditions.
Voltage drop in the UAE
Low voltage supplies in the UAE are 230 V single phase and 400 V three phase at 50 Hz, and cables are sized in mm². In Dubai, Sharjah, Abu Dhabi and Ajman the local electricity authority’s regulations and the consultant’s specification set the design rules, so check the allowed drop and cable sizes against the approved drawings. High summer temperatures in roof spaces and cable routes lower the current a cable can carry, which is a separate check from voltage drop.
Questions
What voltage is used in the UAE?
230 V single phase and 400 V three phase, at 50 Hz.
What voltage drop is allowed?
It depends on the regulations and specification for your project. BS 7671 suggests 3% for lighting and 5% for other uses where the installation is fed from a public low voltage supply. Always use the limit you have been given.
Why does a longer cable need a bigger size?
Resistance grows with length, so the same current loses more voltage. A larger cross-section lowers the resistance per metre.