For MEP contractors, fit-out teams and home owners in Dubai, Sharjah, Abu Dhabi and Ajman. Enter the room size in metres, the lumens and watts of the fitting, and the lux you want, and get the number of fittings, the lux achieved and the load in W/m², using the lumen method.
Worked example
With the calculator’s starting values:
| Find | Fittings for a target lux |
|---|---|
| Room length | 6 m |
| Room width | 5 m |
| Target lux | 500 lux |
| Light output per fitting | 3,600 lm |
| Power per fitting | 36 W |
| Utilisation factor | 0.6 |
| Maintenance factor | 0.8 |
| Fittings needed | 9 fittings |
|---|---|
| Average lux achieved | 518 lux |
| Total lighting load | 324 W |
| Lighting power density | 10.8 W/m² |
| Suggested grid (length × width) | 3 × 3 fittings |
How it is calculated
Room area = length × width
Useful lumens per fitting = lumens × utilisation factor × maintenance factor
Fittings = target lux × area ÷ useful lumens per fitting, rounded up
Lux achieved = fittings × useful lumens per fitting ÷ area
Load density = fittings × watts ÷ area
Lux is lumens per square metre on the working plane. The lumen method gives the average level across the room; it does not show dark corners or glare, so a lighting design with software is still the check for a project you will submit.
Defaults you can change
The 3,600 lm, 36 W fitting, the 0.6 utilisation factor and the 0.8 maintenance factor are example values. Take the lumens and watts from the fitting data sheet, and the utilisation factor from the maker’s photometric tables for your room shape and surface colours. Dark walls and high ceilings lower it.
Lighting in the UAE
Lighting for offices, shops and homes in Dubai, Sharjah, Abu Dhabi and Ajman is designed in lux, with LED panels and downlights sold by the piece and their lumens and watts on the data sheet. Check the target levels in the consultant’s specification or the approved lighting design. Ceiling voids get hot in summer, so choose fittings rated for the ambient temperature on their data sheet.
Questions
What lux is used for offices?
EN 12464-1 gives 500 lux for writing, typing, reading and data processing. Your project specification may set its own figure.
How many lux is one lumen per m²?
One. 1 lux = 1 lumen per square metre.
Why round the number of fittings up?
Rounding down would leave the room below the target. Round up, then arrange the fittings in an even grid.