Lighting Lux Calculator UAE: How Many Light Fittings a Room Needs

For MEP contractors, fit-out teams and home owners in Dubai, Sharjah, Abu Dhabi and Ajman. Enter the room size in metres, the lumens and watts of the fitting, and the lux you want, and get the number of fittings, the lux achieved and the load in W/m², using the lumen method.

Fittings needed9 fittings

Worked example

With the calculator’s starting values:

Inputs
FindFittings for a target lux
Room length6 m
Room width5 m
Target lux500 lux
Light output per fitting3,600 lm
Power per fitting36 W
Utilisation factor0.6
Maintenance factor0.8
Results
Fittings needed9 fittings
Average lux achieved518 lux
Total lighting load324 W
Lighting power density10.8 W/m²
Suggested grid (length × width)3 × 3 fittings

How it is calculated

Room area = length × width

Useful lumens per fitting = lumens × utilisation factor × maintenance factor

Fittings = target lux × area ÷ useful lumens per fitting, rounded up

Lux achieved = fittings × useful lumens per fitting ÷ area

Load density = fittings × watts ÷ area

Lux is lumens per square metre on the working plane. The lumen method gives the average level across the room; it does not show dark corners or glare, so a lighting design with software is still the check for a project you will submit.

Defaults you can change

The 3,600 lm, 36 W fitting, the 0.6 utilisation factor and the 0.8 maintenance factor are example values. Take the lumens and watts from the fitting data sheet, and the utilisation factor from the maker’s photometric tables for your room shape and surface colours. Dark walls and high ceilings lower it.

Lighting in the UAE

Lighting for offices, shops and homes in Dubai, Sharjah, Abu Dhabi and Ajman is designed in lux, with LED panels and downlights sold by the piece and their lumens and watts on the data sheet. Check the target levels in the consultant’s specification or the approved lighting design. Ceiling voids get hot in summer, so choose fittings rated for the ambient temperature on their data sheet.

Questions

What lux is used for offices?

EN 12464-1 gives 500 lux for writing, typing, reading and data processing. Your project specification may set its own figure.

How many lux is one lumen per m²?

One. 1 lux = 1 lumen per square metre.

Why round the number of fittings up?

Rounding down would leave the room below the target. Round up, then arrange the fittings in an even grid.