Al Safat U-Value Compliance Checker Dubai

For consultants, contractors and villa owners building in Dubai: build up a roof, external wall or exposed floor from its layers in mm, or enter a tested U-value, and check it against the Al Sa’fat limit in W/m²K for your rating.

U-value0.523 W/m²K

Worked example

With the calculator’s starting values:

Inputs
ElementExternal wall
Al Sa’fat ratingSilver
U-value fromLayer build-up
Layer 1 thickness20 mm
Layer 1 conductivity1 W/mK
Layer 2 thickness200 mm
Layer 2 conductivity0.9 W/mK
Layer 3 thickness50 mm
Layer 3 conductivity0.034 W/mK
Layer 4 thickness15 mm
Layer 4 conductivity0.5 W/mK
Roof limit0.3 W/m²K
Wall and exposed floor limit, Silver0.57 W/m²K
Wall and exposed floor limit, Golden and Platinum0.42 W/m²K
Conductivity of added insulation0.034 W/mK
Results
U-value0.523 W/m²K
VerdictMeets the limit
Limit for this element0.57 W/m²K
Margin (limit minus U-value)0.047 W/m²K

How it is calculated

Layer resistance R = thickness (m) ÷ conductivity (W/mK)

U-value = 1 ÷ (Rsi + R1 + R2 + R3 + R4 + Rse)

Rsi = 0.10 for roofs, 0.13 for walls, 0.17 for floors; Rse = 0.04 m²K/W

Extra insulation (mm) = (1 ÷ limit − 1 ÷ U) × conductivity × 1000

The surface resistances are the conventional values from ISO 6946. Consultants’ software may use slightly different values, and it also allows for thermal bridges, fixings and air gaps, which this quick check leaves out.

The limits used

Al Sa’fat, the Dubai Green Building System published by Dubai Municipality, sets a maximum U-value of 0.3 W/m²K for roofs, and 0.57 W/m²K for external walls and exposed floors at Silver, or 0.42 W/m²K at Golden and Platinum, in the edition we checked. Limits checked November 2026. All three are inputs, so you can change them if the current edition says otherwise. Confirm the requirement with Dubai Municipality or your consultant.

This is a quick check against the published code. The approving authority and the project consultant have the final say.

Defaults you can change

The four layers are an example wall: 20 mm render, 200 mm block, 50 mm XPS board and 15 mm plaster, with typical conductivities. Hollow blocks in particular vary widely, so use the manufacturer’s tested figures, or switch to “Known U-value” if you have a tested or calculated value for the whole element.

Thermal insulation in the UAE

Al Sa’fat applies to new buildings in Dubai. Abu Dhabi uses its own Estidama Pearl rating system, and projects in Sharjah and Ajman follow their own municipality requirements, so use the limits that apply to your plot. Al Sa’fat also has an average U-value rule for the whole envelope that this tool does not check; ask your consultant whether it applies to your building.

Questions

What is a U-value?

The heat that passes through 1 m² of the element for each degree of temperature difference, in W/m²K. Lower is better insulated.

Does the limit change with the rating?

In the edition we checked, the wall and exposed floor limit drops from 0.57 at Silver to 0.42 at Golden and Platinum, and the roof limit is 0.3 at all three.

Can a plain block wall meet the limit?

With the example values, render, 200 mm block and plaster without the insulation layer give about 2.26 W/m²K, far above 0.57. That is why insulated blocks or an insulation layer are used. Check with your block’s tested figure.